RECOMMENDED_ACTIONThe RECOMMENDED_ACTION parameter displays a text string
that gives a recommended course of action to take based on which type and which specific event of the
alarms is active.
FD_SIMULATE
When simulation is enabled the Field Diagnostics conditions are taken from the Diagnostic Simulate
Value, or else the conditions are taken from Diagnostic Value, and the RECOMMENDED_ACTION
parameter displays the text 'Simulation Active'.
ATTENTION
Note that FD_SIMULATE can be enabled only if the simulation jumper is
enabled in the device. For more information refer section 7.6
MAINTENANCE_MODE
It indicates if the device is available for maintenance. When the resource block is in OOS mode,
MAINTENANCE_MODE parameter displays the text as 'Chk with Oper' i.e., the device is in process
and is not available for maintenance. When the resource block is in AUTO mode,
MAINTENANCE_MODE parameter displays the text as 'Avail for Maint' i.e., the device is out of
process and is available for maintenance. The same text is displayed on the Advanced Display.
'Chk with Oper'- Check with operator to determine availability.
'Avail for Maint'- The device is available for maintenance.
SERIAL_NO
The SERIAL_NO parameter shows the device serial number as obtained from the Sensor housing.
COMM_SERIAL_NO
The COMM_SERIAL_NO parameter is the serial number of the Communication board.
Rev.5
FOUNDATION Fieldbus Option User's Manual
Page 21