Ci: Technology Controller Setpoint 1 / Tec_Ctrl Setp 1; Ci: Technology Controller Setpoint 2 / Tec_Ctrl Setp 2; Technology Controller Setpoint 1 Scaling; Technology Controller Setpoint 2 Scaling - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
Re bit 02 = 1:
When the PID controller is de-activated via p2200, the output signal r2294 is set directly to zero.
Re bit 03 = 0:
The actual values are not limited by p2267 and p2268.
Re bit 03 = 1:
The actual values are limited by p2267 and p2268.
p2253[0...n]

CI: Technology controller setpoint 1 / Tec_ctrl setp 1

VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: Unsigned32 / FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
-
Description:
Sets the signal source for the setpoint 1 of the technology controller.
Dependency:
Refer to: p2254, p2255
p2254[0...n]

CI: Technology controller setpoint 2 / Tec_ctrl setp 2

VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: Unsigned32 / FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
-
Description:
Sets the signal source for the setpoint 2 of the technology controller.
Dependency:
Refer to: p2253, p2256
p2255
Technology controller setpoint 1 scaling / Tec_ctrl set1 scal
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
0.00 [%]
Description:
Sets the scaling for the setpoint 1 of the technology controller.
Dependency:
Refer to: p2253
p2256
Technology controller setpoint 2 scaling / Tec_ctrl set2 scal
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
0.00 [%]
Description:
Sets the scaling for the setpoint 2 of the technology controller.
Dependency:
Refer to: p2254
536
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: PERCENT
Max
-
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: PERCENT
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
100.00 [%]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
100.00 [%]
List Manual (LH2), 04/2014, A5E03263479A
Access level: 2
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
100.00 [%]
Access level: 3
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
100.00 [%]
SINAMICS G130/G150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents