p0015
Macro drive unit / Macro drv unit
CU_G130_DP,
Can be changed: C1
CU_G130_PN,
Data type: Unsigned32
CU_G150_DP,
P-Group: -
CU_G150_PN
Not for motor type: -
Min
0
Description:
Runs the corresponding macro files.
The selected macro file must be available on the memory card/device memory.
Example:
p0015 = 6 --> the macro file PM000006.ACX is run.
Dependency:
Refer to: p0700, p1000, p1500, r8570
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
When executing a specific macro, the corresponding programmed settings are made and become active.
Note:
The macros in the specified directory are displayed in r8570. r8570 is not in the expert list of the commissioning
software.
Macros available as standard are described in the technical documentation of the particular product.
p0016
Activate BOP user-defined list / BOP user list act
CU_G130_DP,
Can be changed: C1, U, T
CU_G130_PN,
Data type: Integer16
CU_G150_DP,
P-Group: -
CU_G150_PN
Not for motor type: -
Min
0
Description:
Setting for activating/de-activating the user-defined list for the Basic Operator Panel (BOP).
If p0016 = 1, then it is only possible to access parameters in the parameter list (p0013).
Value:
0:
1:
Dependency:
Refer to: p0011, p0012, p0013
Note:
The user-defined list can only be de-activated with p0011 = p0012
r0018
Control Unit firmware version / CU FW version
CU_G130_DP,
Can be changed: -
CU_G130_PN,
Data type: Unsigned32
CU_G150_DP,
P-Group: -
CU_G150_PN
Not for motor type: -
Min
0
Description:
Displays the firmware version of the Control Unit.
Dependency:
Refer to: r0128, r0148, r0158, r0197, r0198
Note:
Example:
The value 1010100 should be interpreted as V01.01.01.00.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
BOP user-defined list de-activated
BOP user-defined list activated
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
999999
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
4294967295
2 Parameters
2.2 List of parameters
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
45