Assignment Parameter 10 In Reference To P514[9] / Bicolist10_Ref10; Controller Gain System Of Units / Ctrl_Gain Unit_Sys - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

The significance of the assignment parameters is as follows:
p523[0] BiCo number assigned p514[8] (reference quantity 09)
..
p523[19] BiCo number assigned p514[8] (reference quantity 09)
Dependency:
Refer to: p0514
p0524[0...19]

Assignment parameter 10 in reference to p514[9] / BiCoList10_ref10

B_INF, VECTOR_G
Can be changed: T
Data type: Unsigned32
P-Group: Communications
Not for motor type: -
Min
0
Description:
Assignment parameter for user-specific scaling.
By indexing the assignment parameter p524[0..19], a total of 20 BiCos are available, which should be scaled
corresponding to the user-specific scaling.
The significance of the assignment parameters is as follows:
p524[0] BiCo number assigned p514[9] (reference quantity 10)
..
p524[19] BiCo number assigned p514[9] (reference quantity 10)
Dependency:
Refer to: p0514
p0528

Controller gain system of units / Ctrl_gain unit_sys

ENC
Can be changed: C2(5)
Data type: Integer16
P-Group: Applications
Not for motor type: -
Min
0
Description:
Sets the system of units for the controller gains.
Value:
0:
1:
Note:
For p0528 = 0 (physical/%), the following applies:
Using p0505, the dependent parameters can be changed over between physical and % representation.
For SERVO (r0107) the following applies:
The parameter is pre-assigned a value of 0 and cannot be changed.
p0528
Controller gain system of units / Ctrl_gain unit_sys
VECTOR_G
Can be changed: C2(5)
Data type: Integer16
P-Group: Applications
Not for motor type: -
Min
0
Description:
Sets the system of units for the controller gains.
Value:
0:
1:
Note:
For VECTOR (r0107) the following applies:
The parameter is pre-assigned a value of 1 and cannot be changed.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Representation physical/% (p0505)
Representation no dimensions (referred)
Representation physical/% (p0505)
Representation no dimensions (referred)
Calculated: CALC_MOD_ALL
Dyn. index: -
Units group: -
Scaling: -
Max
4294967295
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1