Tm31 Reset Parameters / Tm31 Par Reset; Tm54F Reset Parameters / Tm54F Par Reset; Reset Drive Parameters / Drive Par Reset - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

p0970

TM31 reset parameters / TM31 par reset

TM31
Can be changed: C2(30)
Data type: Unsigned16
P-Group: Factory settings
Not for motor type: -
Min
0
Description:
The parameter is used to initiate a reset of the parameters on Terminal Module 31 (TM31).
The sampling time p4099 is not reset if in so doing a conflict occurs with the basic clock cycle.
Parameter p0151 is not reset. It is only reset if the entire drive unit is reset to the factory settings (p0976).
Value:
0:
1:
100:
Dependency:
Refer to: p0010
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note:
A factory setting run can only be started if p0010 was first set to 30 (parameter reset).
At the end of the calculations, p0970 is automatically set to 0.
p0970

TM54F reset parameters / TM54F par reset

TM54F_MA
Can be changed: C2(30)
Data type: Unsigned16
P-Group: Factory settings
Not for motor type: -
Min
0
Description:
The parameter is used to initiate a reset of the parameters on Terminal Module 54F (TM54F).
Parameter p0151 is not reset. It is only reset if the entire drive unit is reset to the factory settings (p0976).
Value:
0:
1:
5:
6:
100:
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note:
A factory setting run can only be started if p0010 was first set to 30 (parameter reset).
At the end of the calculations, p0970 is automatically set to 0.
Parameter reset has been completed if p0970 and p0010 have been set to 0.
For p0970 = 5 the following applies:
The password for Safety Integrated must be set.
When Safety Integrated is enabled, this can result in error messages, which then require an acceptance test to be
performed.
Then save the parameters and carry out a POWER ON.
p0970

Reset drive parameters / Drive par reset

VECTOR_G
Can be changed: C2(30)
Data type: Unsigned16
P-Group: Factory settings
Not for motor type: -
Min
0
Description:
The parameter is used to initiate the reset of the parameters of an individual drive unit.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Inactive
Start a parameter reset
Start a BICO interconnection reset
Inactive
Start a parameter reset
Starts a safety parameter reset
Start reset non-safety/safety parameters
Start a BICO interconnection reset
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
100
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
100
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
100
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
277

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents