2 Parameters
2.2 List of parameters
p0264

Cooling unit run-on time / RKA run-on time

B_INF (Cool_unit),
Can be changed: U, T
VECTOR_G
Data type: FloatingPoint32
(Cool_unit)
P-Group: Converter
Not for motor type: -
Min
0.0 [s]
Description:
Sets the run-up time of the cooling unit after a power-off command.
r0265.0...3

BO: Cooling unit control word / RKA STW

B_INF (Cool_unit),
Can be changed: -
VECTOR_G
Data type: Unsigned8
(Cool_unit)
P-Group: Commands
Not for motor type: -
Min
-
Description:
Displays the control word for the cooling unit.
Bit field:
Bit
00
01
02
03
p0266[0...7]

BI: Cooling unit feedback signals signal source / RKA fdbk S_src

B_INF (Cool_unit),
Can be changed: U, T
VECTOR_G
Data type: Unsigned32 / Binary
(Cool_unit)
P-Group: Communications
Not for motor type: -
Min
-
Description:
Sets the signal sources for the feedback signals from the cooling unit.
Index:
[0] = Cooling unit powered up
[1] = Cooling unit ready to be powered up
[2] = Cooling unit no alarm present
[3] = Cooling unit no fault present
[4] = Cooling unit no leaked liquid
[5] = Cooling unit liquid flow OK
[6] = Cooling unit conductivity < fault threshold
[7] = Cooling unit conductivity < alarm threshold
r0267.0...7

BO: Cooling unit status word / RKA ZSW

B_INF (Cool_unit),
Can be changed: -
VECTOR_G
Data type: Unsigned16
(Cool_unit)
P-Group: Commands
Not for motor type: -
Min
-
Description:
Displays the status word of the cooling unit.
Bit field:
Bit
00
01
02
03
04
114
Signal name
Power up cooling unit
Message converter off
Acknowledge faults
Leakage sensing OK
Signal name
RKA powered up
RKA ready to be powered up
RKA no alarm present
RKA no fault present
RKA no leaked fluid
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
180.0 [s]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
Activating
OFF
Acknowledgement
No leaked liquid
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: 9795
Unit selection: -
Expert list: 1
Factory setting
30.0 [s]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
De-activating
ON
No acknowledgement
Leaked liquid
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
No
No