Power Unit Application / Pu Application; Rated Power Unit Power / Pu P_Rated - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Bit field:
Bit
00
01
02
03
04
05
06
07
08
09
12
13
14
15
Note:
For parallel circuit configurations, the parameter index is assigned to a power unit.
p0205

Power unit application / PU application

VECTOR_G
Can be changed: C2(1, 2)
Data type: Integer16
P-Group: Converter
Not for motor type: -
Min
0
Description:
Overloading the load duty cycles applies under the prerequisite that before and after the overload, the drive converter
is operated with its base load current - in this case, a load duty cycle of 300 s is used as basis.
For booksize drive units, the following applies:
Only the setting p0205 = 0 can be selected. In this particular case, the base load current has a load duty cycle of 150
% for 60 s and 176 % for 30 s.
For chassis units, the following applies:
The base load current for a low overload condition is based on a load duty cycle 110 % for 60 s and 150 % for 10 s.
The base load current for a high overload condition is based on a load duty cycle 150 % for 60 s and 160 % for 10 s.
Value:
0:
1:
6:
7:
Note:
When the parameter is changed, all of the motor parameters and the control mode are pre-assigned according to the
selected application.
The parameter has no influence when calculating the thermal overload.
p0205 can only be changed to the settings that are saved in the power unit EEPROM.
The parameter value is not reset when the factory setting is restored (see p0010 = 30, p0970).
r0206[0...4]

Rated power unit power / PU P_rated

B_INF, VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Converter
Not for motor type: -
Min
- [kW]
Description:
Displays the rated power unit power for various load duty cycles.
Index:
[0] = Rated value
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = S1 cont duty cyc
[4] = S6 load duty cycle
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Signal name
Device type
RFI filter available
Active Line Module available
Smart Line Module available
Basic Line Module available with thyristor
bridge
Basic Line Module available with diode
bridge
Liquid cooling with cooling unit (chassis PU) Yes
F3E regenerative feedback into the line
supply
Internal Braking Module
Different cooling type supported
Safe Brake Control (SBC) supported
Safety Integrated supported
Internal LC output filter
Line voltage
Load duty cycle with high overload for vector drives
Load duty cycle with low overload for vector drives
S1 duty cycle for servo drives (feed drive)
S6 duty cycle for servo drives (spindle drive)
1 signal
DC/AC device
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
1-phase
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
7
Calculated: -
Dyn. index: -
Units group: 14_6
Scaling: -
Max
- [kW]
2 Parameters
2.2 List of parameters
0 signal
AC/AC device
No
No
No
No
No
No
No
No
No
Yes
No
No
3-phase
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
6
Access level: 2
Func. diagram: -
Unit selection: p0100
Expert list: 1
Factory setting
- [kW]
FP
-
-
-
-
-
-
-
-
-
-
-
-
-
-
103