Si Motion Transition Time Stop C To Sos (Motor Module); Si Motion Transition Time Stop D To Sos (Motor Module); Si Motion Transition Time Stop E To Sos (Motor Module); Si Motion Transition Time Stop F To Stop B (Motor Module) - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

p9352
SI Motion transition time STOP C to SOS (Motor Module) / SI Mtn t C->SOS MM
VECTOR_G
Can be changed: C2(95)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [µs]
Description:
Sets the transition time from STOP C to "Safe Operating Stop" (SOS).
Dependency:
Refer to: p9552
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
The set time is rounded internally to an integer multiple of the monitoring clock (p9500/p9300) cycle.
SOS: Safe Operating Stop
p9353
SI Motion transition time STOP D to SOS (Motor Module) / SI Mtn t D->SOS MM
VECTOR_G
Can be changed: C2(95)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [µs]
Description:
Sets the transition time from STOP D to "Safe Operating Stop" (SOS).
Dependency:
Refer to: p9553
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
The set time is rounded internally to an integer multiple of the monitoring clock (p9500/p9300) cycle.
SOS: Safe Operating Stop
p9354
SI Motion transition time STOP E to SOS (Motor Module) / SI Mtn t E->SOS MM
VECTOR_G
Can be changed: C2(95)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [µs]
Description:
Sets the transition time from STOP E to "Safe Operating Stop" (SOS).
Dependency:
Refer to: p9554
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
The set time is rounded internally to an integer multiple of the monitoring clock (p9500/p9300) cycle.
SOS: Safe Operating Stop
p9355
SI Motion transition time STOP F to STOP B (Motor Module) / SI Mtn t F->B MM
VECTOR_G
Can be changed: C2(95)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [µs]
Description:
Sets the transition time from STOP F to STOP B.
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
The set time is rounded internally to an integer multiple of the monitoring clock (p9500/p9300) cycle.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
600000000.00 [µs]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
600000000.00 [µs]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
600000000.00 [µs]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
600000000.00 [µs]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 2819
Unit selection: -
Expert list: 1
Factory setting
100000.00 [µs]
Access level: 3
Func. diagram: 2819
Unit selection: -
Expert list: 1
Factory setting
100000.00 [µs]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
100000.00 [µs]
Access level: 3
Func. diagram: 2819
Unit selection: -
Expert list: 1
Factory setting
0.00 [µs]
853