Warning:
The acceleration precontrol r1518 is kept at the old value if the ramp-function generator tracking (r1199.5) is active or
the ramp-function generator output is set (r1199.3). This is used to avoid torque peaks. Depending on the application,
it may therefore be necessary to disable the ramp-function generator tracking (p1145 = 0) or the acceleration
precontrol (p1496 = 0).
The acceleration precontrol is set to zero, if the Vdc control is active (r0056.14/15).
Note:
The parameter is set to 100% by the rotating measurement (refer to p1960).
The acceleration pre-control may not be used if the speed setpoint manifests significant ripple (e.g. analog setpoint)
and the rounding-off in the speed ramp-function generator is disabled.
We also recommend that the pre-control mode is not used if there is gearbox backlash.
p1497[0...n]

CI: Moment of inertia scaling signal source / M_inert scal s_src

VECTOR_G (n/M)
Can be changed: U, T
Data type: Unsigned32 / FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
-
Description:
Sets the signal source for scaling the motor moment of inertia.
p1498[0...n]

Load moment of inertia / Load M_inertia

VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: -
Min
0.00000 [kgm²]
Description:
Sets the load moment of inertia.
Note:
(p0341 * p0342) + p1498 influence the speed/torque pre-control in encoderless operation.
p1499[0...n]

Accelerating for torque control scaling / a for M_ctrl scal

VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
0.0 [%]
Description:
Sets the scaling for the acceleration integrator at low speeds (only for encoderless torque control).
Dependency:
Refer to: p0341, p0342
p1500[0...n]

Macro Connector Inputs (CI) for torque setpoints / Macro CI M_set

VECTOR_G
Can be changed: C2(1), T
Data type: Unsigned32
P-Group: Commands
Not for motor type: REL
Min
0
Description:
Runs the corresponding macro files.
The Connector Inputs (CI) for the torque setpoints of the appropriate Command Data Set (CDS) are appropriately
interconnected.
The selected macro file must be available on the memory card/device memory.
Example:
p1500 = 6 --> the macro file PM000006.ACX is run.
Dependency:
Refer to: p0015, p0700, p1000, r8573
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: PERCENT
Max
-
Calculated: -
Dyn. index: DDS, p0180
Units group: 25_1
Scaling: -
Max
100000.00000 [kgm²]
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
400.0 [%]
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: -
Max
999999
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 5042, 5210,
6030, 6031
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: 5042, 5210
Unit selection: p0100
Expert list: 1
Factory setting
0.00000 [kgm²]
Access level: 3
Func. diagram: 6030
Unit selection: -
Expert list: 1
Factory setting
100.0 [%]
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0