Note:
The interface configuration (p8900 and following) is activated with p8905.
The active DHCP mode is displayed in parameter r8914.
The parameter is not influenced by setting the factory setting.
If value = 0:
DHCP deactivated.
If value = 1:
Reserved.
If value = 2:
DHCP activated. The MAC address of this interface is used for client identification.
If value = 3:
DHCP activated. The station name of this interface is used for client identification.
p8905

IE Interface configuration / IE IF config

CU_G130_DP,
Can be changed: U, T
CU_G130_PN,
Data type: Integer16
CU_G150_DP,
P-Group: -
CU_G150_PN
Not for motor type: -
Min
0
Description:
Setting to activate the interface configuration for the Industrial Ethernet interface (X127) on the Control Unit.
p8905 is automatically set to 0 at the end of an operation.
Value:
0:
1:
2:
3:
Dependency:
Refer to: p8900, p8901, p8902, p8903
Note:
Re p8905 = 1:
The interface configuration (p8900 and following) is activated.
Re p8905 = 2:
The interface configuration (p8900 and following) is activated and saved to non-volatile memory.
Re p8905 = 3:
The interface configuration is reset to the factory setting at all points.
The factory settings for the interface configuration are loaded on activation (p8905 = 1) or at the next POWER ON.
p8908

Activate FTP / Act FTP

CU_G130_DP,
Can be changed: U, T
CU_G130_PN,
Data type: Integer16
CU_G150_DP,
P-Group: -
CU_G150_PN
Not for motor type: -
Min
0
Description:
Activation of the FTP server.
Permits the FTP access to the /INSTALL/SINAMICS directory of the memory card.
Value:
0:
1:
Note:
Activation of the FTP server becomes effective immediately.
Deactivation only becomes effective after POWER ON of the Control Unit.
Before commissioning the system for the first time, the FTP server is activated independent of the parameter setting.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
No function
Activate configuration
Activate and save configuration
Delete configuration
No
Yes
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
3
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0