2 Parameters
2.2 List of parameters
Dependency:
Refer to: r0209, p0210, r1214
p1208[0...1]

BI: AR modification infeed / AR modification

VECTOR_G
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Functions
Not for motor type: -
Min
-
Description:
Sets the signal source to modify the automatic restart (AR).
Interconnections between the automatic restart and infeed:
With the following interconnection in the mode p1210 = 6, the automatic restart can respond to infeed faults:
BI: p1208[0] = r2139.3
With the following interconnection, in the mode p1210 = 4, the automatic restart can respond to line supply failure of
the infeed:
BI: p1208[1] = r0863.2
Index:
[0] = Infeed fault
[1] = Infeed line supply failure
Dependency:
Refer to: r0863, r2139
p1210

Automatic restart mode / AR mode

B_INF
Can be changed: U, T
Data type: Integer16
P-Group: Functions
Not for motor type: -
Min
0
Description:
Sets the automatic restart mode (AR).
Value:
0:
1:
6:
Dependency:
The automatic restart requires an active ON command (e.g., via a digital input). If, for p1210 > 1, there is no active
ON command, then the automatic restart is interrupted.
When using an Advanced Operator Panel (AOP) in the LOCAL Mode, then there is no automatic restart.
Refer to: p0840, p0857, p1267
Danger:
If the automatic restart is activated (p1210 > 1) if there is an ON command (refer to p0840), the drive is powered up
as soon as any fault messages that are present can be acknowledged. This also occurs after the line supply returns
or the Control Unit boots if the DC link voltage is again present or the feedback of the line supply infeed (refer to
p0864) is again available. This automatic power-up sequence can only be interrupted by withdrawing the ON
command.
Notice:
A change is only accepted and made in the state "initialization" (r1214.0) and "wait for alarm" (r1214.1).
For p1210 > 1, the infeed is automatically started.
Note:
When automatic restart mode is activated, the supply voltage must remain connected (e.g. backed up by UPS).
Re p1210 = 1:
Faults that are present are automatically acknowledged. If new faults occur after a successful fault acknowledgment,
then these are also automatically acknowledged again. A minimum time of p1212 + 1 s must expire between a
successful fault acknowledgement and a fault re-occurring if the signal ON/OFF1 (STW1.0) is at a HIGH signal level.
If the signal ON/OFF1 is at a LOW signal level, then the time between a successful fault acknowledgement and a
new fault must be at least 1 s. p1211 has no influence on the number of acknowledgment attempts.
Re p1210 = 6:
An automatic restart is carried out if any fault has occurred.
316
Inhibit automatic restart
Acknowledge all faults without restarting
Restart after fault with additional start attempts
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
6
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0