r3978
BICO CounterDevice / BICO CounterDevice
CU_G130_DP,
Can be changed: -
CU_G130_PN,
Data type: Unsigned32
CU_G150_DP,
P-Group: Commands
CU_G150_PN
Not for motor type: -
Min
-
Description:
Displays the counter reading for modified BICO interconnections on this device.
The counter is incremented by one for each modified BICO interconnection.
r3979
BICO counter drive object / BICO counter DO
B_INF, ENC, HUB,
Can be changed: -
TB30, TM150, TM31,
Data type: Unsigned32
TM54F_MA,
P-Group: Commands
TM54F_SL,
Not for motor type: -
VECTOR_G
Min
-
Description:
Displays the counter reading for modified BICO interconnections on this drive object.
The counter is incremented by one for each modified BICO interconnection.
p3981
Faults acknowledge drive object / Faults ackn DO
All objects
Can be changed: U, T
Data type: Unsigned8
P-Group: Messages
Not for motor type: -
Min
0
Description:
Setting to acknowledge all active faults of a drive object.
Notice:
Safety messages cannot be acknowledged using this parameter.
Note:
Parameter should be set from 0 to 1 to acknowledge.
After acknowledgement, the parameter is automatically reset to 0.
p3985
Master control mode selection / PcCtrl mode select
B_INF, VECTOR_G
Can be changed: U, T
Data type: Integer16
P-Group: Setpoints
Not for motor type: -
Min
0
Description:
Sets the mode to change over the master control / LOCAL mode.
Value:
0:
1:
Danger:
When changing the master control in operation, the drive can manifest undesirable behavior - e.g. it can accelerate
up to another setpoint.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Change master control for STW1.0 = 0
Change master control in operation
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1
2 Parameters
2.2 List of parameters
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 2
Func. diagram: 8060
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
597