2 Parameters
2.2 List of parameters
r1773[0...1]
Motor model slip speed / MotMod slip
VECTOR_G (n/M)
Can be changed: -
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL, FEM
Min
- [rpm]
Description:
Displays estimated (speed) signals of the motor model.
r1773[0]: Displays the estimated (mechanical) slip of the motor model.
r1773[1]: Displays the estimated input speed of the motor model.
Index:
[0] = Slip speed estimated
[1] = Speed estimated
p1774[0...n]
Motor model offset voltage compensation alpha / MotMod offs comp A
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: PEM, REL, FEM
Min
-5.000 [V]
Description:
Sets the offset voltage in the alpha direction; this compensates the offset voltages of the drive converter/inverter at
low speeds. The value is valid for the rated (nominal) pulse frequency of the power unit.
Note:
The value is pre-set during the rotating measurement.
p1775[0...n]
Motor model offset voltage compensation beta / MotMod offs comp B
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: PEM, REL, FEM
Min
-5.000 [V]
Description:
Sets the offset voltage in the beta direction; this compensates the offset voltages of the drive converter/inverter at low
speeds. The value is valid for the rated (nominal) pulse frequency of the power unit.
Note:
The value is pre-set during the rotating measurement.
r1776[0...6]
Motor model status signals / MotMod status sig
VECTOR_G (n/M)
Can be changed: -
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
-
Description:
Displays the internal status signals of the motor model:
Index 0: Changeover ramp between current and voltage models
Index 1: Changeover ramp for model tracking (encoderless induction motors only)
Index 2: Changeover ramp for zero frequency range (encoderless induction motors only)
Index 3: Transition ramp actual speed from speed setpoint to model value (encoderless FEM)
Index 4: Speed controller enable (encoderless FEM)
Index 5: Transition ramp between current and voltage models (encoderless FEM)
Index 6: Transition ramp for EMF deviation at PLL input (encoderless PESM)
424
Calculated: -
Dyn. index: -
Units group: 3_1
Scaling: -
Max
- [rpm]
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
5.000 [V]
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
5.000 [V]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: p0505
Expert list: 1
Factory setting
- [rpm]
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.000 [V]
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.000 [V]
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
SINAMICS G130/G150