p0629[0...n]

Stator resistance reference / R_stator ref

VECTOR_G (n/M)
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: PEM, REL, FEM
Min
0.00000 [ohm]
Description:
Reference value for the identification of the stator resistance every time the drive is powered up.
Dependency:
The measurement of the reference value is activated by the automatic calculation (p0340 = 1, 2), if the following
conditions apply:
- the motor temperature is at this instant in time less than 30 °C (r0035).
- a KTY temperature sensor is not being used (p0601).
Refer to: p0621, r0623
Note:
The reference value to identify the stator resistance should be manually entered after the first identification (p0629 =
r0623). The identification must be realized when the motor is in a cold state, as the value refers to the ambient
temperature p0625. The feeder cable resistance should be entered into p0352 before the measurement.
The result must be saved after the first measurement so that the reference is available after the CU has a powered
up. When changing p0350 or p0352, the reference value p0629 should be re-determined.
r0630[0...n]

Mot_temp_mod ambient temperature / Mod T_ambient

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: REL, FEM
Min
- [°C]
Description:
Displays the ambient temperature of the motor temperature model (models 2 and 3).
r0631[0...n]

Mot_temp_mod stator iron temperature / Mod T_stator

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: REL, FEM
Min
- [°C]
Description:
Displays the stator iron temperature of the motor temperature model (models 2 and 3).
r0632[0...n]

Mot_temp_mod stator winding temperature / Mod T_winding

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: REL, FEM
Min
- [°C]
Description:
Displays the stator winding temperature of the motor temperature model (models 2 and 3).
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: CALC_MOD_EQU
Dyn. index: MDS, p0130
Units group: 16_1
Scaling: -
Max
2000.00000 [ohm]
Calculated: -
Dyn. index: MDS, p0130
Units group: 21_1
Scaling: p2006
Max
- [°C]
Calculated: -
Dyn. index: MDS, p0130
Units group: 21_1
Scaling: p2006
Max
- [°C]
Calculated: -
Dyn. index: MDS, p0130
Units group: 21_1
Scaling: p2006
Max
- [°C]
2 Parameters
2.2 List of parameters
Access level: 4
Func. diagram: -
Unit selection: p0349
Expert list: 1
Factory setting
0.00000 [ohm]
Access level: 4
Func. diagram: 8017
Unit selection: p0505
Expert list: 1
Factory setting
- [°C]
Access level: 4
Func. diagram: 8017
Unit selection: p0505
Expert list: 1
Factory setting
- [°C]
Access level: 4
Func. diagram: 8017
Unit selection: p0505
Expert list: 1
Factory setting
- [°C]