Pre-Assigned Binectors And Connectors; Switch Symbol; Symbols For Logic Functions; Symbols For Computational And Closed-Loop Control Functions - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Pre-assigned binectors and connectors

Fixed percentage values
Fixed value 1 [%]
-10 000.00...10 000.00 [%]
p2900[D]
p2900[D] (0.00)
Fixed value 2 [%]
-10 000.00...10 000.00 [%]
p2901[D]
p2901[D] (0.00)
Fixed values [%]
p2902[0...14] (0.00)
r2902[0...14]
p2902[0] = +0 %
p2902[5] = +100 %
p2902[10] = -20 %
p2902[1] = +5 %
p2902[6] = +150 %
p2902[11] = -50 %
p2902[2] = +10 %
p2902[7] = +200 %
p2902[12] = -100 %
p2902[3] = +20 %
p2902[8] = -5 %
p2902[13] = -150 %
p2902[4] = +50 %
p2902[9] = -10 %
p2902[14] = -200 %
Fixed speed values
n_set_fixed 1
-210 000.000...210 000.000 [1/min]
p1001[D]
p1001[D] (0.000)
n_set_fixed 15
-210 000.000...210 000.000 [1/min]
p1015[D]
p1015[D] (0.000)
Fixed torque value
Fixed value M [Nm]
-100 000.00...100 000.00 [Nm]
p2930[D]
p2930[D] (0.00)

Switch symbol

pxxxx
Simple changeover switch
0
The switch position is shown according to
the factory setting (in this case, switch
1
position 1 in the default state on delivery).
1
2
DO: All objects
Explanations on the function diagrams - Explanation of the symbols (part 2)

Symbols for logic functions

Logical inversion
1
AND element with logical
&
inversion of an input signal
R/S flip-flop
R Q
S = setting input
R = reset input
S Q
Q = non-inverted output
= inverted output
Q
With a simultaneous 1-signal at the R and
S inputs, the S input dominates.
x
1
y
Exclusiv-OR/XOR
=1
y = 1 when x
x
is.
x
1
2
2
x
1
y
Comparator
=
y = 1 when x
= x
is.
1
2
x
2
Symbols for computational and
closed-loop control functions
x
y
Sign reversal
-1
y = -x
x
y
Absolute value generator
y = |x|
Divider
x
1
y
x
1
y =
x
x
2
2
x
1
y
Multiplier
y = x
* x
x
1
2
2
Comparator
x
y
>0
y = 1 if the analog signal x > 0, i.e. is
positive.
Differentiator
dx
x
y
dt
dx
Y =
dt
Symbol for monitoring
Monitoring
Axxxxx
Monitoring
or
In the bottom right-hand corner of
Fxxxxx
the diagram.
3
4
Symbols for computational and closed-loop
control functions
S
1
y
x
0
S
1
y
x
0
S
1
y
x
0
H
S
1
y
x
0
H
LU
MLU
y
x
LL
MLL
SET
S & H
x
y
5
6
Function diagram
fp_1021_51_eng.vsd
SINAMICS
07.11.13 V04.07.00
Threshold value switch 1/0
Outputs at y a logical "1" if x < S.
Threshold value switch 0/1
Outputs at y a logical "1" if x > S.
Threshold value 1/0 with hysteresis
Outputs a logical "1" at y if x < S.
If x >= S + H then y returns to 0.
Threshold value 0/1 with hysteresis
Outputs a logical "1" at y if x > S.
If x <= S - H then y returns to 0.
Limiter
x is limited to the upper limit LU and the lower limit
LL and output at y.
The digital signals MLU and MLL have the value
"1", if the upper or lower limit is active.
Sample & Hold element
Sample and hold element.
y = x if SET = 1
(not retentively saved at POWER OFF)
7
8
- 1021 -