Profibus Status / Pb Status - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

[19] = PZD 20
[20] = PZD 21
[21] = PZD 22
[22] = PZD 23
[23] = PZD 24
[24] = PZD 25
[25] = PZD 26
[26] = PZD 27
[27] = PZD 28
[28] = PZD 29
[29] = PZD 30
[30] = PZD 31
[31] = PZD 32
Bit field:
Bit
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
Dependency:
Refer to: p2051, p2061
Note:
IF1: Interface 1
r2054

PROFIBUS status / PB status

CU_G130_DP,
Can be changed: -
CU_G150_DP
Data type: Integer16
P-Group: Communications
Not for motor type: -
Min
0
Description:
Status display for the PROFIBUS interface.
Value:
0:
1:
2:
3:
4:
Note:
Re r2054 = 3:
In state 3 (the LED flashes green), a cyclic connection has been established to the PROFIBUS master; however, one
of the following prerequisites is missing for cyclic operation:
- No setpoints are being received as the PROFIBUS master is in the STOP condition.
Only for clock-cycle synchronous operation, the following applies:
- The drive is not in synchronism as the global control (GC) has an error.
Re r2054 = 4:
In the status 4 (LED green), the cyclic connection to the PROFIBUS master has been established and setpoints are
being received. The clock cycle synchronization is OK, the global control (GC) is error-free.
This state does not provide any statement regarding the quality of the clock cycle synchronous sign-of-life characters
on the drive objects.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Signal name
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
OFF
No connection (search for baud rate)
Connection OK (baud rate found)
Cyclic connection with master (data exchange)
Cyclic data OK
1 signal
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
4
2 Parameters
2.2 List of parameters
0 signal
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Access level: 3
Func. diagram: 2410
Unit selection: -
Expert list: 1
Factory setting
-
FP
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
477

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130