If1/If2 Pzd Functionality Selection / If1/If2 Pzd Fct; Cbe2X Remote Controller Number / Cbe2X Rem Ctrl Num; Cbe20 Firmware Selection / Cbe20 Fw Sel - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

p8815[0...1]

IF1/IF2 PZD functionality selection / IF1/IF2 PZD fct

CU_G130_DP,
Can be changed: C1(1)
CU_G130_PN,
Data type: Integer16
CU_G150_DP,
P-Group: Communications
CU_G150_PN
Not for motor type: -
Min
1
Description:
Selects the PZD interface for the clock cycle synchronization functionality and PROFIsafe.
Value:
1:
2:
Index:
[0] = Isochronous mode
[1] = PROFIsafe
Dependency:
Refer to: p8839
Note:
A change only becomes effective after POWER ON, reset or project download.
Example:
p8815[0] = 1: IF1 supports the isochronous mode.
p8815[1] = 2: IF2 supports PROFIsafe.
p8829

CBE2x remote controller number / CBE2x rem ctrl num

CU_G130_DP
Can be changed: C1(1)
(PROFINET CBE20),
Data type: Integer16
CU_G130_PN
P-Group: Communications
(PROFINET CBE20),
Not for motor type: -
CU_G150_DP
(PROFINET CBE20),
Min
CU_G150_PN
1
(PROFINET CBE20)
Description:
Sets the number of remote controllers expected for PROFINET CBE20/CBE25.
The "Shared Device" functionality is activated with a value = 2.
The drive is being accessed by two PROFINET controllers simultaneously:
- automation controller (SIMOTION or SIMATIC A-CPU).
- safety controller (SIMATIC F-CPU).
Value:
1:
2:
Notice:
The F CPU may only use PROFIsafe telegrams.
The A CPU must be connected to enable the F CPU to gain access.
Set the value = 1 to commission the F CPU individually.
Note:
A change only becomes effective after a POWER ON.
p8835

CBE20 firmware selection / CBE20 FW sel

CU_G130_DP
Can be changed: C1(1)
(PROFINET CBE20),
Data type: Integer16
CU_G130_PN
P-Group: Communications
(PROFINET CBE20),
Not for motor type: -
CU_G150_DP
(PROFINET CBE20),
Min
CU_G150_PN
1
(PROFINET CBE20)
Description:
Selects the firmware version for the CBE20.
Value:
1:
2:
3:
4:
99:
Note:
A change only becomes effective after a POWER ON.
The parameter is not influenced by setting the factory setting.
CBE20: Communication Board Ethernet 20
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Interface 1 (IF1)
Interface 2 (IF2)
Automation or Safety
Automation and Safety
PROFINET Device
PN gate
SINAMICS Link
EtherNet/IP
Customer-specific from the OEM directory
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
2
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
2
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
99
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: 2198
Unit selection: -
Expert list: 1
Factory setting
1
785