r1315

Voltage boost total / U_boost total

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: U/f open-loop control
Not for motor type: -
Min
- [Vrms]
Description:
Displays the total resulting voltage boost in volt.
r1315 = p1310 + p1311 + p1312
Dependency:
Refer to: p1310, p1311, p1312
p1320[0...n]

U/f control programmable characteristic frequency 1 / Uf char f1

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: U/f open-loop control
Not for motor type: -
Min
0.00 [Hz]
Description:
The programmable characteristic for the U/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the first point along the characteristic.
Dependency:
Selects the freely programmable characteristic using p1300 = 3.
The following applies to the frequency values: p1320 <= p1322 <= p1324 <= p1326. Otherwise, a standard
characteristic is used that contains the rated motor operating point.
Refer to: p1300, p1310, p1311, p1321, p1322, p1323, p1324, p1325, p1326, p1327
Note:
Linear interpolation is carried out between the points 0 Hz/p1310, p1320/p1321 ... p1326/p1327.
The voltage boost when accelerating (p1311) is also applied to the freely programmable U/f characteristic.
p1321[0...n]

U/f control programmable characteristic voltage 1 / Uf char U1

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: U/f open-loop control
Not for motor type: -
Min
0.0 [Vrms]
Description:
The programmable characteristic for the U/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the first point along the characteristic.
Dependency:
Selects the freely programmable characteristic using p1300 = 3.
Refer to: p1310, p1311, p1320, p1322, p1323, p1324, p1325, p1326, p1327
Note:
Linear interpolation is carried out between the points 0 Hz/p1310, p1320/p1321 ... p1326/p1327.
The voltage boost when accelerating (p1311) is also applied to the freely programmable U/f characteristic.
p1322[0...n]

U/f control programmable characteristic frequency 2 / Uf char f2

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: U/f open-loop control
Not for motor type: -
Min
0.00 [Hz]
Description:
The programmable characteristic for the U/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the second point along the characteristic.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: -
Scaling: p2001
Max
- [Vrms]
Calculated: CALC_MOD_ALL
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
3000.00 [Hz]
Calculated: CALC_MOD_ALL
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
10000.0 [Vrms]
Calculated: CALC_MOD_ALL
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
3000.00 [Hz]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 6301
Unit selection: -
Expert list: 1
Factory setting
- [Vrms]
Access level: 3
Func. diagram: 6301
Unit selection: -
Expert list: 1
Factory setting
0.00 [Hz]
Access level: 3
Func. diagram: 6301
Unit selection: -
Expert list: 1
Factory setting
0.0 [Vrms]
Access level: 3
Func. diagram: 6301
Unit selection: -
Expert list: 1
Factory setting
0.00 [Hz]
351