3. POSITIONING SIGNAL
Downloaded from
ManualsNet.com
(13) RLS signal (M1612+20n)
(a)The RLS signal is controlled by the ON/OFF status of the lower stroke end
limit switch input (FLS) to the A172SENC from an external source.
• Lower stroke end limit switch input OFF ...... RLS signal: ON
• Lower stroke end limit switch input ON ........ RLS signal: OFF
(b) The status of the lower stroke end limit switch input (RLS) when the RLS
signal is ON/OFF is indicated in the figure below.
RLS signal: ON
A172SENC
RLS
COM
(14) STOP signal (M1613+20n)
(a) The STOP signal is controlled by the ON/OFF status of the stop signal
(STOP) sent to the A172SENC from an external source.
• Stop signal OFF ..... STOP signal: OFF
• Stop signal ON ....... STOP signal: ON
(b) The status of the external stop switch (STOP) when the STOP signal is
ON/OFF is indicated in the figure below.
STOP signal: ON
A172SENC
STOP
(15) DOG/CHANGE signal (M1614+20n)
(a) The DOG signal is set to ON/OFF by proximity dog signal input (DOG) to
the A172SENC during zeroing.
The CHANGE signal is set to ON/OFF by speed/position switching signal
input (CHANGE) during speed/position switching control.
(b) A contact input or B contact input can be selected by system setting.
search engine
RLS
STOP
COM
3 − 11
RLS signal: OFF
A172SENC
RLS
RLS
COM
STOP signal: OFF
A172SENC
STOP
STOP
COM