ABB Relion 670 Series Applications Manual page 99

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UUS F
Section 6
6.1
C37.118 Phasor Measurement Data Streaming Protocol
Configuration PMUCONF
6.1.1
Identification
Function description
Configuration parameters for IEEE
1344 and C37.118 protocol
6.1.2
Application
The IED supports the following IEEE synchrophasor standards:
IEEE 1344-1995 (Both measurements and data communication)
IEEE Std C37.118-2005 (Both measurements and data communication)
IEEE Std C37.118.1–2011 and C37.118.1a-2014 (Measurements)
IEEE Std C37.118.2-2011 (Data communication)
PMUCONF contains the PMU configuration parameters for both IEEE C37.118 and IEEE 1344
protocols. This means all the required settings and parameters in order to establish and define a
number of TCP and/or UDP connections with one or more PDC clients (synchrophasor client). This
includes port numbers, TCP/UDP IP addresses, and specific settings for IEEE C37.118 as well as
IEEE 1344 protocols.
6.1.3
Operation principle
The Figure
can support communication with maximum 8 TCP clients and 6 UDP client groups, simultaneously.
Every client can communicate with only one instance of the two available PMUREPORT function
block instances at a time. It means that one client cannot communicate with both PMUREPORT:1
and PMUREPORT:2 at the same time. However, multiple clients can communicate with the same
instance of PMUREPORT function block at the same time. For TCP clients, each client can decide to
communicate with an existing instance of PMUREPORT by knowing the corresponding PMU ID for
that PMUREPORT instance. Whereas, for UDP clients, the PMUREPORT instance for each UDP
channel is defined by the user in the PMU and the client has to know the PMU ID corresponding to
that instance in order to be able to communicate. More information is available in the sections
Short guidance for the use of TCP
Bay control REC670
Application manual
Wide area measurement system
IEC 61850
identification
33
demonstrates the communication configuration diagram. As can be seen, the IED
and
© Copyright 2017 ABB. All rights reserved
IEC 60617
identification
PMUCONF
-
Short guidance for the use of
Wide area measurement system
GUID-747C6AD7-E6A1-466E-92D1-68865681F92F v1
GUID-1E140EA0-D198-443A-B445-47CEFD2E6134 v1
ANSI/IEEE C37.2
device number
-
GUID-33694C62-A109-4D8F-9063-CEFA5D0E78BC v4
GUID-2608FBC4-9036-476A-942B-13452019BC11 v2
UDP.