ABB Relion 670 Series Applications Manual page 470

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 17
Monitoring
Operation
The operation of Disturbance report function DRPRDRE has to be set
Disabled is selected, note that no disturbance report is registered, and none sub-function will
operate (the only general parameter that influences Sequential of events (SOE)).
Operation = Disabled :
Disturbance reports are not stored.
LED information (yellow - pickup, red - trip) is not stored or changed.
Operation = Enabled :
Disturbance reports are stored, disturbance data can be read from the local HMI and from a
PC for example using PCM600.
LED information (yellow - pickup, red - trip) is stored.
Every recording will get a number (0 to 999) which is used as identifier (local HMI, disturbance
handling tool and IEC 61850). An alternative recording identification is date, time and sequence
number. The sequence number is automatically increased by one for each new recording and is
reset to zero at midnight. The maximum number of recordings stored in the IED is 100. The oldest
recording will be overwritten when a new recording arrives (FIFO).
17.6.3.1
Recording times
Prefault recording time (
disturbance. The setting should be at least
pre-fault values in the Trip value recorder (TVR) function.
Postfault recording time (
of the trig-signal (does not influence the Trip value recorder (TVR) function).
Recording time limit (
the recording time if some trigging condition (fault-time) is very long or permanently set (does
not influence the Trip value recorder (TVR) function).
Operation in test mode
If the IED is in test mode and
any recordings and no LED information is displayed.
464
To be able to delete disturbance records,
The maximum number of recordings depend on each recordings total recording
time. Long recording time will reduce the number of recordings to less than 100.
The IED flash disk should NOT be used to store any user files. This might cause
disturbance recordings to be deleted due to lack of disk space.
PreFaultRecT ) is the recording time before the starting point of the
PostFaultRecT ) is the maximum recording time after the disappearance
TimeLimit ) is the maximum recording time after trig. The parameter limits
OpModeTest = Disabled . Disturbance report function does not save
© Copyright 2017 ABB. All rights reserved
Operation parameter has to be Enabled .
0.1 s to ensure enough samples for the estimation of
1MRK 511 401-UUS F
M12179-82 v7
Enabled or Disabled . If
M12179-88 v6
M12179-492 v4
Bay control REC670
Application manual