Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UUS F
V
=
V
0
+
1
EQUATION2020-ANSI V1 EN-US
Where
V
phase
R
f
Z
0
The fault current, in the fault point, can be calculated as:
=
I
3I
j
0
EQUATION2021 V1 EN-US
The impedance Z
point apparatus) the impedance is equal to the capacitive coupling between the phase conductors
and ground:
= -
Z
0
EQUATION2022-ANSI V1 EN-US
Where
I
j
X
c
In a system with a neutral point resistor (resistance grounded system) the impedance Z
calculated as:
-
jX 3R
=
Z
0
-
jX
EQUATION1946 V1 EN-US
Where
R
n
Bay control REC670
Application manual
phase
×
3 R
f
Z
0
is the phase voltage in the fault point before the fault,
is the resistance to ground in the fault point and
is the system zero sequence impedance to ground
×
3 V
=
phase
+ ×
Z
3 R
0
f
is dependent on the system grounding. In an isolated system (without neutral
0
×
3 V
= -
phase
jX
j
c
I
j
is the capacitive ground fault current at a non-resistive phase-to-ground fault
is the capacitive reactance to ground
×
c
n
+
3R
c
n
is the resistance of the neutral point resistor
© Copyright 2017 ABB. All rights reserved
Section 8
Current protection
(Equation 49)
(Equation 50)
(Equation 51)
can be
0
(Equation 52)