Section 8
Current protection
No.
StartMode
21
LatchedStart
22
FollowStart
23
FollowStart
24
FollowStart
25
FollowStart&
Mode
Table continues on next page
188
RetripMode
t1 and t2 initiated
with
Always
external START
Off
external START
UseFunctionM
external START
ode
Always
external START
Off
external START
and current above
set level
© Copyright 2017 ABB. All rights reserved
When t1 has elapsed,
When t2 or t2MPh
TRRET will
has elapsed, TRBU
will be given if
always be given
current is above set
level *) and higher
than I>BlkCBPos or
CBCLDLx input has
logical value one
when current is
smaller than
I>BlkCBPos
never be given
current is above set
level *) and higher
than I>BlkCBPos or
CBCLDLx input has
logical value one
when current is
smaller than
I>BlkCBPos
be given if current
current is above set
is above set level of
level *) and higher
IPh> and higher
than I>BlkCBPos or
than I>BlkCBPos or
CBCLDLx input has
CBCLDLx input has
logical value one
logical value one
when current is
when current is
smaller than
smaller than
I>BlkCBPos
I>BlkCBPos
be given if external
current is above set
START is present
level *) and higher
than I>BlkCBPos or
CBCLDLx input has
logical value one
when current is
smaller than
I>BlkCBPos
never be given
current is above set
level *) and higher
than I>BlkCBPos or
CBCLDLx input has
logical value one
when current is
smaller than
I>BlkCBPos
1MRK 511 401-UUS F
t1 and t2 and t2MPh
will be stopped
(reset) if
t1 and (t2 or
t2MPh) and 150ms
expires and
current is below
set level *) or
CBCLDLx input has
logical value zero
external START
disappears
external START
disappears
external START
disappears
current is below
set level *) or
external START
disappears
Bay control REC670