ABB Relion 670 Series Applications Manual page 573

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UUS F
Bay control REC670
Application manual
Preprocessing block shall only be used to feed functions within the same execution
cycles (e.g. use preprocessing block with cycle 1 to feed transformer differential
protection). The only exceptions are measurement functions (CVMMXN,
CMMXU,VMMXU, etc.) which shall be fed by preprocessing blocks with cycle 8.
When two or more preprocessing blocks are used to feed one protection function
(e.g. over-power function GOPPDOP), it is of outmost importance that parameter
setting DFTReference has the same set value for all of the preprocessing blocks
involved
© Copyright 2017 ABB. All rights reserved
Section 23
Basic IED functions
567

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec670

Table of Contents