ABB Relion 670 Series Applications Manual page 471

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UUS F
If the IED is in test mode and
mode and the status is indicated in the saved recording.
Post Retrigger
Disturbance report function does not automatically respond to any new trig condition during a
recording, after all signals set as trigger signals have been reset. However, under certain
circumstances the fault condition may reoccur during the post-fault recording, for instance by
automatic reclosing to a still faulty power line.
In order to capture the new disturbance it is possible to allow retriggering (
during the post-fault time. In this case a new, complete recording will pickup and, during a period,
run in parallel with the initial recording.
When the retrig parameter is disabled (
until the post-fault (
the post-fault period and lasts longer than the proceeding recording a new complete recording
will be started.
Disturbance report function can handle a maximum of 3 simultaneous disturbance recordings.
17.6.3.2
Binary input signals
Up to 352 binary signals can be selected among internal logical and binary input signals. The
configuration tool is used to configure the signals.
For each of the 352 signals, it is also possible to select if the signal is to be used as a trigger for
the start of the Disturbance report and if the trigger should be activated on positive (1) or
negative (0) slope.
TrigDRN : Disturbance report may trig for binary input N ( Enabled ) or not ( Disabled ).
TrigLevelN : Trig on positive ( Trig on 1 ) or negative ( Trig on 0 ) slope for binary input N.
Func103N : Function type number (0-255) for binary input N according to IEC-60870-5-103, that is,
128: Distance protection, 160: overcurrent protection, 176: transformer differential protection and
192: line differential protection.
Info103N : Information number (0-255) for binary input N according to IEC-60870-5-103, that is,
69-71: Trip L1-L3, 78-83: Zone 1-6.
See also description in the chapter IEC 60870-5-103.
17.6.3.3
Analog input signals
Up to 40 analog signals can be selected among internal analog and analog input signals. PCM600
is used to configure the signals.
The analog trigger of Disturbance report is not affected if analog input M is to be included in the
disturbance recording or not (
Bay control REC670
Application manual
OpModeTest = Enabled . Disturbance report function works in normal
PostFaultrecT or TimeLimit ) period is terminated. If a new trig occurs during
For retrieving remote data from LDCM module, the Disturbance report function
should be connected to a 8 ms SMAI function block if this is the only intended use
for the remote data.
OperationM = Enabled / Disabled ).
© Copyright 2017 ABB. All rights reserved
PostRetrig = Disabled ), a new recording will not pickup
Section 17
Monitoring
M12155-173 v7
PostRetrig = Enabled )
M12179-90 v9
M12179-92 v6
465