Section 4
Analog inputs
4.2.2.5
Example on how to connect a wye connected three-phase CT set to the IED
Figure
13
gives an overview of the actions which are needed to make this measurement available to the
built-in protection and control functions within the IED as well.
A
CT 600/5
Wye Connected
Protected Object
ANSI13000002 V3 EN-US
Figure 13:
Wye connected three-phase CT set with wye point towards the protected object
64
It is recommended to:
use 1A rated CT input into the IED in order to connect CTs with 1A and 2A
secondary rating
use 5A rated CT input into the IED in order to connect CTs with 5A and 10A
secondary rating
gives an example about the wiring of a wye connected two-phase CT set to the IED. It
For correct terminal designations, see the connection diagrams valid for the
delivered IED.
B
C
I_A
I_B
I_C
© Copyright 2017 ABB. All rights reserved
IED
1
2
3
1MRK 511 401-UUS F
SEMOD55055-352 v11
4
SMAI_20
ANSI13000002-3-en.vsd
Bay control REC670
Application manual