Section 8
Current protection
2ndHarmStab : Operate level of 2nd harmonic current restrain set in % of the fundamental current.
The setting range is
ANSI09000636 V1 EN-US
Figure 60: Directional function characteristic
1.
RCA = Relay characteristic angle
2.
ROA = Relay operating angle
3.
Reverse
4.
Forward
8.2.3.1
Settings for each step
DirModeSelx : The directional mode of step x . Possible settings are Disabled / Non-directional /
Forward / Reverse .
Characteristx : Selection of time characteristic for step x . Definite time delay and different types of
inverse time characteristics are available according to Table 19.
136
5 - 100 % in steps of 1%. The default setting is 20%.
3
2
x means step 1, 2, 3 and 4.
© Copyright 2017 ABB. All rights reserved
V
ref
1
2
4
I
dir
ANSI09000636-1-en.vsd
1MRK 511 401-UUS F
M12982-19 v10
Bay control REC670
Application manual