1MRK 511 401-UUS F
14.4.2.4
Configuration setting
If there is no bypass busbar and therefore no 789 disconnector, then the interlocking for 789 is not
used. The states for 789, 7189G, BB7_D, BC_17, BC_27 are set to open by setting the appropriate
module inputs as follows. In the functional block diagram, 0 and 1 are designated 0=FALSE and
1=TRUE:
•
789_OP = 1
•
789_CL = 0
•
7189G_OP = 1
•
7189G_CL = 0
•
BB7_D_OP = 1
•
BC_17_OP = 1
•
BC_17_CL = 0
•
BC_27_OP = 1
•
BC_27_CL = 0
•
EXDU_BPB = 1
•
VP_BB7_D = 1
•
VP_BC_17 = 1
•
VP_BC_27 = 1
If there is no second busbar WA2 and therefore no 289 disconnector, then the interlocking for 289
is not used. The state for 289, 2189G, BC_12, BC_27 are set to open by setting the appropriate
module inputs as follows. In the functional block diagram, 0 and 1 are designated 0=FALSE and
1=TRUE:
•
289_OP = 1
•
289_CL = 0
•
2189G_OP = 1
•
2189G_CL = 0
•
BC_12_CL = 0
•
BC_27_OP = 1
•
BC_27_CL = 0
•
VP_BC_12 = 1
14.4.3
Interlocking for bus-coupler bay ABC_BC (3)
Bay control REC670
Application manual
© Copyright 2017 ABB. All rights reserved
Section 14
Control
M13560-108 v4
IP14144-1 v2
333