ABB Relion 670 Series Applications Manual page 345

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UUS F
BBTR_OP = 1
VP_BBTR = 1
14.4.4
Interlocking for transformer bay AB_TRAFO (3)
14.4.4.1
Application
The interlocking for transformer bay (AB_TRAFO, 3) function is used for a transformer bay
connected to a double busbar arrangement according to figure 145. The function is used when
there is no disconnector between circuit breaker and transformer. Otherwise, the interlocking for
line bay (ABC_LINE, 3) function can be used. This function can also be used in single busbar
arrangements.
189
152
252
389
ANSI04000515 V1 EN-US
Figure 145: Switchyard layout AB_TRAFO (3)
The signals from other bays connected to the module AB_TRAFO are described below.
14.4.4.2
Signals from bus-coupler
If the busbar is divided by bus-section disconnectors into bus-sections, the busbar-busbar
connection could exist via the bus-section disconnector and bus-coupler within the other bus-
section.
Bay control REC670
Application manual
WA1 (A)
WA2 (B)
289
189G
AB_TRAFO
289G
389G
252 and 489G are not
used in this interlocking
489G
489
en04000515_ansi.vsd
© Copyright 2017 ABB. All rights reserved
Section 14
Control
IP14149-1 v2
M13567-3 v7
M13566-4 v4
M13566-6 v4
339