ABB Relion 670 Series Applications Manual page 391

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UUS F
Table 44: Blockings without setting possibilities
Activation
Disconnected
transformer
(automatically reset)
No Master/More than
one Master
(automatically reset)
One transformer in a
parallel group switched
to manual control
(automatically reset)
Communication error
(COMMERR)
(automatic deblocking)
Circulating current method
Mutual blocking
When one parallel instance of voltage control TR8ATCC (90) blocks its operation, all other
TR8ATCCs (90) working in parallel with that module, shall block their operation as well. To achieve
this, the affected TR8ATCC (90) function broadcasts a mutual block to the other group members
via the horizontal communication. When mutual block is received from any of the group members,
automatic operation is blocked in the receiving TR8ATCCs (90) that is, all units of the parallel
group.
The following conditions in any one of TR8ATCCs (90) in the group will cause mutual blocking
when the circulating current method is used:
Bay control REC670
Application manual
Type of blocking
Description
Auto Block
Automatic control is blocked for a transformer
when parallel control with the circulating current
method is used, and that transformer is
disconnected from the LV-busbar. (This is under
the condition that the setting
selected
Otherwise the transformer will get into the state
Homing). The binary input signal DISC in TR1ATCC
(90) or TR8ATCC (90) function shall be used to
supervise if the transformer LV circuit breaker is
closed or not. The outputs TRFDISC and AUTOBLK
will be activated . Blocking will be removed when
the transformer is reconnected (input signal DISC
set back to zero).
Auto Block
Automatic control is blocked when parallel control
with the master-follower method is used, and the
master is disconnected from the LV-busbar. Also
if there for some reason should be a situation
with more than one master in the system, the
same blocking will occur. The binary input signal
DISC in TR1ATCC (90) or TR8ATCC (90) function
shall be used to supervise if the transformer LV
circuit breaker is closed or not. The outputs
TRFDISC, MFERR and AUTOBLK will be activated.
The followers will also be blocked by mutual
blocking in this situation. Blocking will be
removed when the transformer is reconnected
(input signal DISC set back to zero).
Auto Block
When the setting
automatic control will be blocked when parallel
control with the master-follower or the circulating
current method is used, and one of the
transformers in the group is switched from auto
to manual. The output AUTOBLK will be activated.
Auto block
If the horizontal communication (GOOSE) for any
one of TR8ATCCs (90) in the group fails it will
cause blocking of automatic control in all
TR8ATCC (90) functions, which belong to that
parallel group. This error condition will be reset
automatically when the communication is re-
established. The outputs COMMERR and
AUTOBLK will be set.
© Copyright 2017 ABB. All rights reserved
OperHoming is
Off for the disconnected transformer.
OperationAdapt is " Disabled ",
Section 14
Control
SEMOD159053-285 v4
385