Section 17
Monitoring
Setting
k
VGenZeroDb
IGenZeroDb
VBase (set in
Global base)
IBase (set in
Global base)
17.2
Gas medium supervision SSIMG (63)
17.2.1
Identification
Function description
Insulation gas monitoring function
17.2.2
Application
Gas medium supervision (SSIMG ,63) is used for monitoring the circuit breaker condition. Proper
arc extinction by the compressed gas in the circuit breaker is very important. When the pressure
becomes too low compared to the required value, the circuit breaker operation shall be blocked to
minimize the risk of internal failure. Binary information based on the gas pressure in the circuit
breaker is used as an input signal to the function. The function generates alarms based on the
received information.
17.2.3
Setting guidelines
The parameters for Gas medium supervision SSIMG can be set via local HMI or Protection and
Control Manager PCM600.
Operation : This is used to disable/enable the operation of gas medium supervision i.e. Off/On.
PresAlmLimit : This is used to set the limit for a pressure alarm condition in the circuit breaker.
PresLOLimit : This is used to set the limit for a pressure lockout condition in the circuit breaker.
TempAlarmLimit : This is used to set the limit for a temperature alarm condition in the circuit
breaker.
TempLOLimit : This is used to set the limit for a temperature lockout condition in the circuit
breaker.
tPressureAlarm : This is used to set the time delay for a pressure alarm indication, given in s.
454
Short description
Low pass filter coefficient for
power measurement, V and I
Zero point clamping in % of
Vbase
Zero point clamping in % of
Ibase
Base setting for voltage level
in kV
Base setting for current level
in A
IEC 61850
identification
SSIMG
© Copyright 2017 ABB. All rights reserved
Selected
Comment
value
0.00
Typically no additional filtering is required
25%
Set minimum voltage level to 25%
3
Set minimum current level to 3%
15,65
Set generator rated phase-to-phase voltage
3690
Set generator rated current
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
63
1MRK 511 401-UUS F
GUID-358AD8F8-AE06-4AEA-9969-46E5299D5B4B v3
GUID-AD96C26E-C3E5-4B21-9ED6-12E540954AC3 v4
GUID-A840E38C-CC42-4995-A569-A6092DDB81B2 v5
GUID-DF6BEC98-F806-41CE-8C29-BEE9C88FC1FD v3
Bay control REC670
Application manual