1MRK 511 401-UUS F
Signal
VP_BC_17
VP_BC_27
EXDU_BC
These signals from each bus-coupler bay (ABC_BC) are needed:
Signal
BC12CLTR
BC17OPTR
BC17CLTR
BC27OPTR
BC27CLTR
VPBC12TR
VPBC17TR
VPBC27TR
EXDU_BC
These signals from each bus-section disconnector bay (A1A2_DC) are also needed. For B1B2_DC,
corresponding signals from busbar B are used. The same type of module (A1A2_DC) is used for
different busbars, that is, for both bus-section disconnector A1A2_DC and B1B2_DC.
Signal
DCOPTR
DCCLTR
VPDCTR
EXDU_DC
If the busbar is divided by bus-section circuit breakers, the signals from the bus-section coupler
bay (A1A2_BS), rather than the bus-section disconnector bay (A1A2_DC) must be used. For
B1B2_BS, corresponding signals from busbar B are used. The same type of module (A1A2_BS) is
used for different busbars, that is, for both bus-section circuit breakers A1A2_BS and B1B2_BS.
Signal
S1S2OPTR
S1S2CLTR
VPS1S2TR
EXDU_BS
Bay control REC670
Application manual
The switch status of BC_17 is valid.
The switch status of BC_27 is valid.
No transmission error from any bus-coupler bay (BC).
A bus-coupler connection through the own bus-coupler exists between busbar
WA1 and WA2.
No bus-coupler connection through the own bus-coupler between busbar WA1
and WA7.
A bus-coupler connection through the own bus-coupler exists between busbar
WA1 and WA7.
No bus-coupler connection through the own bus-coupler between busbar WA2
and WA7.
A bus-coupler connection through the own bus-coupler exists between busbar
WA2 and WA7.
The switch status of BC_12 is valid.
The switch status of BC_17 is valid.
The switch status of BC_27 is valid.
No transmission error from the bay that contains the above information.
The bus-section disconnector is open.
The bus-section disconnector is closed.
The switch status of bus-section disconnector DC is valid.
No transmission error from the bay that contains the above information.
No bus-section coupler connection between bus-sections 1 and 2.
A bus-section coupler connection exists between bus-sections 1 and 2.
The switch status of bus-section coupler BS is valid.
No transmission error from the bay that contains the above information.