ABB Relion 670 Series Applications Manual page 537

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UUS F
SYNCH signal on the MUx function block indicates that protection functions are blocked due
to loss of internal time synchronization to the IED
MUSYNCH signal on the MUx function block monitors the synchronization flag
the datastream and IED hardware time synchronization.
Using MU for time synchronization via PPS
IEC/UCA 61850-9-2LE
IEC10000061 V2 EN-US
Figure 239: Setting example when MU is the synchronizing source
Settings on the local HMI under Main menu/Configuration/Time/Synchronization/
TIMESYNCHGEN:1/IEC61850-9-2:
HwSyncSrc : set to PPS as generated by the MU (ABB MU)
SyncLostMode : set to Block to block protection functions if time synchronization is lost
SyncAccLevel : can be set to 4μs since this corresponds to a maximum phase angle error of
0.072 degrees at 50Hz
Settings on the local HMI under Main menu/Configuration/Time/Synchronization/
TIMESYNCHGEN:1/General:
fineSyncSource can be set to something different to correlate events and data to other IEDs
in the station.
Two status monitoring signals can be:
SYNCH signal on the MUx function block indicates that protection functions are blocked due
to loss of internal time synchronization to the IED.
MUSYNCH signal on the MUx function block monitors the synchronization flag
the datastream and IED hardware time synchronization.
Bay control REC670
Application manual
This example is not valid when GPS time is used for differential protection, when
PTP is enabled or when the PMU report is used.
IED
Analog data
MU
© Copyright 2017 ABB. All rights reserved
PPS
Synchronization
IEC10000061=2=en=Original.vsd
Section 20
Station communication
smpSynch in
smpSynch in
531

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec670

Table of Contents