Section 13
Secondary system supervision
Imin : The minimum pickup level setting should be set as % of IBase . This setting enables the
function to start detecting delta. Typical setting is 10% of
MeasMode : This setting is used to detect the mode of measurement; phase to phase or phase to
ground .
OpMode : This setting is used to select the mode of operation. For protection applications, this
should be set to
DelI> : This setting is used to detect the pickup value for instantaneous sample, RMS, DFT mag
based delta detection. Set a typical value of 200% of
DeltaT : This setting defines the number of old cycles data to be used for delta calculation in
RMS/DFT Mag mode. Typical value is 2 cycles.
tHold : This setting defines the pulse length for supervision pickup signal. Typical value is 100 ms.
EnaHarm2Blk : This setting should be set to ON, to enable blocking for heavy inrush currents or
other sources of 2
Harm2BlkLev : This is the blocking level of 2
Typical setting is 15% of fundamental signal.
EnStValAdap : This setting should be set to ENABLE in special networks where settings in the
network are adapted with respect to 3
Harm3Level : This is the set level of 3
DelI> should be modified. Typical setting is 15% of fundamental signal.
StValGrad : This setting is used to modify the DelI> based on 3
10% to modify the
13.6
Delta supervision of real input DELSPVC
13.6.1
Identification
Function description
Delta supervision of real input
13.6.2
Application
Delta supervision of real input DELSPVC is a general processed input delta supervision. It is used
to configure any processed inputs such as:
Power (S)
Active power (P)
Reactive power (P)
Thermal heat content (ɸ)
Energy
270
Instantaneous 1 cycle old . Load supervision can be done using DFT mag mode.
nd
harmonic injections.
rd
rd
harmonic with respect to fundamental signal at which the
DelI> .
IEC 61850
identification
DELSPVC
© Copyright 2017 ABB. All rights reserved
IBase .
IBase to use this function as fault detection.
nd
harmonic with respect to the fundamental signal.
harmonic level.
rd
harmonic level. Typical setting is
IEC 60617
identification
1MRK 511 401-UUS F
GUID-470F7470-F3D1-46BC-B0EA-CD180FBA0AB2 v1
GUID-66CFBA71-B3A4-489F-B7F4-F1909B75E1DD v1
ANSI/IEEE C37.2
device number
GUID-C7F56ACE-D1F2-4F33-96CA-108D7F11FDD5 v1
Bay control REC670
Application manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec670

Table of Contents