ABB Relion 670 Series Applications Manual page 492

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 17
Monitoring
Setting
MassW3
RLRated
RLHighRated
RLMaxTap
RLMinTap
RatedVoltTap
HighVoltTap
LowVoltTap
JanAmbTmp
FebAmbTmp
MarchAmbTmp
AprilAmbTmp
MayAmbTmp
JuneAmbTmp
JulyAmbTmp
Table continues on next page
486
Short Description
Set the mass of transformer winding 3
when the winding time constant mode
is selected as
Calculated
Set the loss ratio at principal tapping
position for the calculation of ratio
loss at the given tap position
Set the loss ratio at principal tapping
+1 position for the calculation of ratio
loss at the given tap position
Set the loss ratio at maximum tapping
position where maximum voltage is
possible for the calculation of ratio
loss at the given tap position
Set the loss ratio at minimum tapping
position where minimum voltage is
possible for the calculation of ratio
loss at the given tap position
Set the rated voltage tap position
number
Set the tap position number where
maximum voltage is possible
Set the tap position number where
minimum voltage is possible
Set the January month average
ambient temperature for the
calculation of top oil temperature
when ambient temperature sensor
failure/absence
Set the February month average
ambient temperature for the
calculation of top oil temperature
when ambient temperature sensor
failure/absence
Set the March month average ambient
temperature for the calculation of top
oil temperature when ambient
temperature sensor failure/absence
Set the April month average ambient
temperature for the calculation of top
oil temperature when ambient
temperature sensor failure/absence
Set the May month average ambient
temperature for the calculation of top
oil temperature when ambient
temperature sensor failure/absence
Set the June month average ambient
temperature for the calculation of top
oil temperature when ambient
temperature sensor failure/absence
Set the July month average ambient
temperature for the calculation of top
oil temperature when ambient
temperature sensor failure/absence
© Copyright 2017 ABB. All rights reserved
Selected value
10.0 t
3.0
5.0
8.0
11.0
10
19
1
30° C
30° C
30° C
30° C
30° C
30° C
30° C
1MRK 511 401-UUS F
Bay control REC670
Application manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec670

Table of Contents