and configurations must abide by the following rules: Normally apparatus position is connected
with contacts showing both open (b-type) and closed positions (a-type).
WA1_QA1:
BUS1_OP/CL = Position of TIE_QA1 breaker and belonging disconnectors
BUS2_OP/CL = Position of WA2_QA1 breaker and belonging disconnectors
LINE1_OP/CL = Position of LINE1_QB9 disconnector
LINE2_OP/CL = Position of LINE2_QB9 disconnector
VB1OK/FF = Supervision of WA1_MCB fuse
VB2OK/FF = Supervision of WA2_MCB fuse
VL1OK/FF = Supervision of LINE1_MCB fuse
VL2OK/FF = Supervision of LINE2_MCB fuse
Setting
TIE_QA1:
BUS1_OP/CL = Position of WA1_QA1 breaker and belonging disconnectors
BUS2_OP/CL = Position of WA2_QA1 breaker and belonging disconnectors
LINE1_OP/CL = Position of LINE1_QB9 disconnector
LINE2_OP/CL = Position of LINE2_QB9 disconnector
VB1OK/FF = Supervision of WA1_MCB fuse
VB2OK/FF = Supervision of WA2_MCB fuse
VL1OK/FF = Supervision of LINE1_MCB fuse
VL2OK/FF = Supervision of LINE2_MCB fuse
Setting
WA2_QA1:
BUS1_OP/CL = Position of WA1_QA1 breaker and belonging disconnectors
BUS2_OP/CL = Position of TIE_QA1 breaker and belonging disconnectors
LINE1_OP/CL = Position of LINE1_QB9 disconnector
LINE2_OP/CL = Position of LINE2_QB9 disconnector
VB1OK/FF = Supervision of WA1_MCB fuse
VB2OK/FF = Supervision of WA2_MCB fuse
VL1OK/FF = Supervision of LINE1_MCB fuse
VL2OK/FF = Supervision of LINE2_MCB fuse
Setting
If only two SESRSYN functions are provided in the same IED, the connections and settings are
according to the SESRSYN functions for WA1_QA1 and TIE_QA1.
14.1.4
Setting guidelines
The setting parameters for the Synchronizing, synchronism check and energizing check function
SESRSYN (25) are set via the local HMI (LHMI) or PCM600.
This setting guidelines describes the settings of the SESRSYN (25) function via the LHMI.
Common base IED value for primary voltage (
GBASVAL, found under Main menu//Configuration/Power system/GlobalBaseValue/
GBASVAL_X/VBase. The SESRSYN (25) function has one setting for the bus reference voltage
GblBaseSelBus ) and one setting for the line reference voltage ( GblBaseSelLine ) which
(
independently of each other can be set to select one of the twelve GBASVAL functions used for
Bay control REC670
Application manual
CBConfig = 1 1/2 bus CB
CBConfig = Tie CB
CBConfig = 1 1/2 bus alt. CB
© Copyright 2017 ABB. All rights reserved
VBase ) is set in a Global base value function,
Section 14
Control
M12550-3 v14
285