Section 17
Monitoring
the CB would become (10000 – 200) = 9800 operations at the rated operating current after
one operation at 50 kA.
Accumulated energy
Monitoring the contact erosion and interrupter wear has a direct influence on the required
maintenance frequency. Therefore, it is necessary to accurately estimate the erosion of the
contacts and condition of interrupters using cumulative summation of I
on the type of circuit breaker. The energy values were accumulated using the current value and
exponent factor for CB contact opening duration. When the next CB opening operation is started,
the energy is accumulated from the previous value. The accumulated energy value can be reset to
initial accumulation energy value by using the Reset accumulating energy input, RSTIPOW.
Circuit breaker operation cycles
Routine breaker maintenance like lubricating breaker mechanism is based on the number of
operations. A suitable threshold setting helps in preventive maintenance. This can also be used to
indicate the requirement for oil sampling for dielectric testing in case of an oil circuit breaker.
Circuit breaker operation monitoring
By monitoring the activity of the number of operations, it is possible to calculate the number of
days the breaker has been inactive. Long periods of inactivity degrade the reliability for the
protection system.
Circuit breaker spring charge monitoring
For normal circuit breaker operation, the circuit breaker spring should be charged within a
specified time. Detecting a long spring charging time indicates the time for circuit breaker
maintenance. The last value of the spring charging time can be given as a service value.
Circuit breaker gas pressure indication
For proper arc extinction by the compressed gas in the circuit breaker, the pressure of the gas
must be adequate. Binary input available from the pressure sensor is based on the pressure levels
inside the arc chamber. When the pressure becomes too low compared to the required value, the
circuit breaker operation is blocked.
17.4.3
Setting guidelines
The breaker monitoring function is used to monitor different parameters of the circuit breaker.
The breaker requires maintenance when the number of operations has reached a predefined value.
For proper functioning of the circuit breaker, it is also essential to monitor the circuit breaker
operation, spring charge indication or breaker wear, travel time, number of operation cycles and
accumulated energy during arc extinction.
458
© Copyright 2017 ABB. All rights reserved
1MRK 511 401-UUS F