ABB Relion 670 Series Applications Manual page 335

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UUS F
double busbar arrangement without transfer busbar or a single busbar arrangement with/without
transfer busbar.
189
152
989
ANSI04000478 V1 EN-US
Figure 135: Switchyard layout ABC_LINE (3)
The signals from other bays connected to the module ABC_LINE (3) are described below.
14.4.2.2
Signals from bypass busbar
To derive the signals:
Signal
BB7_D_OP
VP_BB7_D
EXDU_BPB
These signals from each line bay (ABC_LINE, 3) except that of the own bay are needed:
Signal
789OPTR
VP789TR
EXDU_BPB
For bay n, these conditions are valid:
Bay control REC670
Application manual
WA1 (A)
WA2 (B)
WA7 (C)
289
789
189G
289G
989G
en04000478_ansi.vsd
All line disconnectors on bypass WA7 except in the own bay are open.
The switch status of disconnectors on bypass busbar WA7 are valid.
No transmission error from any bay containing disconnectors on bypass
busbar WA7
789 is open
The switch status for 789 is valid.
No transmission error from the bay that contains the above information.
© Copyright 2017 ABB. All rights reserved
Section 14
Control
M13560-4 v5
M13560-6 v5