Section 8
Current protection
Table 26: Setting summary for FunctionMode, StartMode, RetripMode and BuTripMode
No.
StartMode
FunctionMode = Current
1
LatchedStart
2
LatchedStart
3
LatchedStart
4
FollowStart
5
FollowStart
6
FollowStart
7
FollowStart&
Mode
8
FollowStart&
Mode
9
FollowStart&
Mode
*) Set level depends on selected BuTripMode, that is, set level can be either IPh> or IN> or both.
No.
StartMode
FunctionMode = CB Pos
10
LatchedStart
11
LatchedStart
Table continues on next page
186
RetripMode
t1 and t2 initiated
with
Off
external START
UseFunctionM
external START
ode
Always
external START
Off
external START
UseFunctionM
external START
ode
Always
external START
Off
external START
and current above
set level
UseFunctionM
external START
ode
and current above
set level
Always
external START
and current above
set level
RetripMode
t1 and t2 initiated
with
Off
external START
UseFunctionM
external START
ode
© Copyright 2017 ABB. All rights reserved
When t1 has elapsed,
When t2 or t2MPh
TRRET will
has elapsed, TRBU
will be given if
never be given
current is above
set level *)
be given if current
current is above
is above set level of
set level *)
IPh>
always be given
current is above
set level *)
never be given
current is above
set level *)
be given if current
current is above
is above set level of
set level *)
IPh>
be given if external
current is above
START is present
set level *)
never be given
current is above
set level *) and
external START
present
be given if current
current is above
is above set level of
set level *) and
IPh> and external
external START
START is present
present
be given if external
current is above
START is present
set level *) and
external START
present
When t1 has elapsed,
When t2 or t2MPh
TRRET will
has elapsed, TRBU
will be given if
never be given
CBCLDLx input has
logical value one
be given if
CBCLDLx input has
CBCLDLx input has
logical value one
logical value one
1MRK 511 401-UUS F
GUID-845257FF-2774-472A-B982-E9DDD8966988 v1
t1 and t2 and t2MPh
will be stopped
(reset) if
t1 and (t2 or t2MPh)
and 150ms expires
and current is
below set level *)
t1 and (t2 or t2MPh)
and 150ms expires
and current is
below set level *)
t1 and (t2 or t2MPh)
and 150ms expires
and current is
below set level *)
external START
disappears
external START
disappears
external START
disappears
current is below set
level *) or external
START disappears
current is below set
level *) or external
START disappears
current is below set
level *) or external
START disappears
t1 and t2 and t2MPh
will be stopped
(reset) if
t1 and (t2 or
t2MPh) and 150ms
expires and
CBCLDLx input has
logical value zero
t1 and (t2 or
t2MPh) and 150ms
expires and
CBCLDLx input has
logical value zero
Bay control REC670
Application manual