Section 2
Application
rings, load transfer logics and so on. The graphical configuration tool ensures simple and fast
testing and commissioning.
Forcing of binary inputs and outputs is a convenient way to test wiring in substations as well as
testing configuration logic in the IEDs. Basically it means that all binary inputs and outputs on the
IED I/O modules (BOM, BIM, IOM & SOM) can be forced to arbitrary values.
Central Account Management is an authentication infrastructure that offers a secure solution for
enforcing access control to IEDs and other systems within a substation. This incorporates
management of user accounts, roles and certificates and the distribution of such, a procedure
completely transparent to the user.
Flexible Product Naming allows the customer to use an IED-vendor independent IEC 61850 model
of the IED. This customer model will be used as the IEC 61850 data model, but all other aspects of
the IED will remain unchanged (e.g., names on the local HMI and names in the tools). This offers
significant flexibility to adapt the IED to the customers' system and standard solution.
2.2

Main protection functions

Table 2:
2
0-3
3-A03
IEC 61850 or
ANSI
function name
Differential protection
HZPDIF
87
34
The following tables list all the functions available in the IED. Those functions that
are not exposed to the user or do not need to be configured are not described in
this manual.
Example of quantities
= number of basic instances
= option quantities
= optional function included in packages A03 (refer to ordering details)
Function description
High impedance differential protection, single phase
© Copyright 2017 ABB. All rights reserved
1MRK 511 401-UUS F
GUID-F5776DD1-BD04-4872-BB89-A0412B4B5CC3 v1
GUID-66BAAD98-851D-4AAC-B386-B38B57718BD2 v15