Section 13
Secondary system supervision
working in an AND-condition, that is, both algorithms must give condition for block in order to
activate the output signals BLKV or BLKZ.
13.2.3.3
Negative sequence based
The relay setting value
set lower than the value that is calculated according to equation 113.
3
V
2
PU
EQUATION1757-ANSI V4 EN-US
where:
V2PU
VBase
The setting of the current limit
must be higher than the normal unbalance current that might exist in the system and can be
calculated according to equation 114.
3
I
2
PU
EQUATION1758-ANSI V4 EN-US
where:
I2
IBase
13.2.3.4
Zero sequence based
The IED setting value
3V0PU should not be set lower than the value that is calculated according to equation 115.
3
V
0
PU
EQUATION1759-ANSI V4 EN-US
where:
3V0
VBase
The setting of the current limit
be higher than the normal unbalance current that might exist in the system. The setting can be
calculated according to equation 116.
262
3V2PU is given in percentage of the base voltage VBase and should not be
V
2
100
VBase
3
is the maximal negative sequence voltage during normal operation conditions, plus a margin of 10...20%
is the base voltage for the function according to the setting
3I2PU is in percentage of parameter IBase . The setting of 3I2PU
I
2
100
IBase
is the maximal negative sequence current during normal operating conditions, plus a margin of 10...20%
is the base current for the function according to the setting
3V0PU is given in percentage of the base voltage VBase . The setting of
3
V
0
100
VBase
3
is the maximal zero sequence voltage during normal operation conditions, plus a margin of 10...20%
is the base voltage for the function according to the setting
3I0PU is done in percentage of IBase . The setting of pickup must
© Copyright 2017 ABB. All rights reserved
GlobalBaseSel
GlobalBaseSel
GlobalBaseSel
Bay control REC670
Application manual
1MRK 511 401-UUS F
M13683-17 v9
(Equation 113)
(Equation 114)
M13683-43 v8
(Equation 115)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec670

Table of Contents