ABB Relion 670 Series Applications Manual page 575

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UUS F
BLOCK
DFTSPFC
^GRP1_A
^GRP1_B
^GRP1_C
^GRP1_N
TYPE
ANSI07000198 V1 EN-US
Figure 252: Configuration for using an instance in task time group 1 as DFT reference
Assume instance SMAI7:7 in task time group 1 has been selected in the configuration to control the
frequency tracking . Observe that the selected reference instance (i.e. frequency tracking master)
must be a voltage type. Observe that positive sequence voltage is used for the frequency tracking
feature.
For task time group 1 this gives the following settings (see Figure
SMAI1:1:
DFTReference = DFTRefGrp7 for SMAI1:1 to use SMAI7:7 as reference (see Figure 252) SMAI2:2 –
SMAI12:12:
For task time group 2 this gives the following settings:
SMAI1:13 – SMAI12:24:
reference (SMAI7:7)
For task time group 3 this gives the following settings:
SMAI1:25 – SMAI12:36:
(SMAI7:7)
Example 2
Bay control REC670
Application manual
SMAI1:1
SPFCOUT
AI3P
AI1
AI2
AI3
AI4
AIN
DFTRefExtOut = DFTRefGrp7 to route SMAI7:7 reference to the SPFCOUT output,
DFTReference = DFTRefGrp7 for SMAI2:2 – SMAI12:12 to use SMAI7:7 as reference.
DFTReference = ExternalDFTRef to use DFTSPFC input of SMAI1:13 as
DFTReference = ExternalDFTRef to use DFTSPFC input as reference
© Copyright 2017 ABB. All rights reserved
SMAI1:13
BLOCK
SPFCOUT
DFTSPFC
AI3P
^GRP1_A
AI1
^GRP1_B
AI2
^GRP1_C
AI3
^GRP1_N
AI4
TYPE
AIN
SMAI1:25
BLOCK
SPFCOUT
DFTSPFC
AI3P
^GRP1_A
AI1
^GRP1_B
AI2
^GRP1_C
AI3
^GRP1_N
AI4
TYPE
AIN
ANSI07000198.vsd
251
Section 23
Basic IED functions
for numbering):
569

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec670