ABB Relion 670 Series Applications Manual page 249

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UUS F
11.1.2.3
Application possibilities
Due to its flexibility the general current and voltage protection (CVGAPC) function can be used,
with appropriate settings and configuration in many different applications. Some of possible
examples are given below:
1.
Transformer and line applications:
2.
Generator protection
11.1.2.4
Inadvertent generator energization
When the generator is taken out of service, and stand-still, there is a risk that the generator circuit
breaker is closed by mistake.
Three-phase energizing of a generator, which is at standstill or on turning gear, causes it to
behave and accelerate similarly to an induction motor. The machine, at this point, essentially
represents the subtransient reactance to the system and it can be expected to draw from one to
four per unit current, depending on the equivalent system impedance. Machine terminal voltage
can range from 20% to 70% of rated voltage, again, depending on the system equivalent
impedance (including the block transformer). Higher quantities of machine current and voltage (3
to 4 per unit current and 50% to 70% rated voltage) can be expected if the generator is connected
Bay control REC670
Application manual
Underimpedance protection (circular, non-directional characteristic) (21)
Underimpedance protection (circular mho characteristic) (21)
Voltage Controlled/Restrained Overcurrent protection (51C, 51V)
Phase or Negative/Positive/Zero Sequence (Non-Directional or Directional) Overcurrent
protection (50, 51, 46, 67, 67N, 67Q)
Phase or phase-to-phase or Negative/Positive/Zero Sequence over/under voltage
protection (27, 59, 47)
Thermal overload protection (49)
Open Phase protection
Unbalance protection
80-95% Stator earth fault protection (measured or calculated 3Vo) (59GN)
Rotor earth fault protection (with external COMBIFLEX RXTTE4 injection unit) (64F)
Underimpedance protection (21)
Voltage Controlled/Restrained Overcurrent protection (51C, 51V)
Turn-to-Turn & Differential Backup protection (directional Negative Sequence.
Overcurrent protection connected to generator HV terminal CTs looking into generator)
(67Q)
Stator Overload protection (49S)
Rotor Overload protection (49R)
Loss of Excitation protection (directional positive sequence OC protection) (40)
Reverse power/Low forward power protection (directional positive sequence OC
protection, 2% sensitivity) (32)
Dead-Machine/Inadvertent-Energizing protection (51/27)
Breaker head flashover protection
Improper synchronizing detection
Sensitive negative sequence generator over current protection and alarm (46)
Phase or phase-to-phase or Negative/Positive/Zero Sequence over/under voltage
protection (27x, 59x, 47)
Generator out-of-step detection (based on directional positive sequence OC) (78)
Inadvertent generator energizing
© Copyright 2017 ABB. All rights reserved
Section 11
Multipurpose protection
SEMOD53443-136 v3