Section 16
Logic
If the BLOCK input is activated, it freezes the logical outputs at the last value.
Table 46: Output signals
Name of OUTx
OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
OUT9
OUT10
OUT11
OUT12
OUT13
OUT14
OUT15
OUT16
The sum of the numbers in column "Value when activated" when all OUTx (1≤x≤16) are active
equals 65535. This is the highest integer that can be converted by the ITBGAPC function block.
16.12
Elapsed time integrator with limit transgression and
overflow supervision TEIGAPC
16.12.1
Identification
Function Description
Elapsed time integrator
16.12.2
Application
The function TEIGAPC is used for user-defined logics and it can also be used for different
purposes internally in the IED. An application example is the integration of elapsed time during the
measurement of neutral point voltage or neutral current at earth-fault conditions.
Settable time limits for warning and alarm are provided. The time limit for overflow indication is
fixed to 999999.9 seconds.
438
Type
Description
BOOLEAN
Output 1
BOOLEAN
Output 2
BOOLEAN
Output 3
BOOLEAN
Output 4
BOOLEAN
Output 5
BOOLEAN
Output 6
BOOLEAN
Output 7
BOOLEAN
Output 8
BOOLEAN
Output 9
BOOLEAN
Output 10
BOOLEAN
Output 11
BOOLEAN
Output 12
BOOLEAN
Output 13
BOOLEAN
Output 14
BOOLEAN
Output 15
BOOLEAN
Output 16
IEC 61850
IEC 60617
identificatio
identificatio
n
n
TEIGAPC
-
© Copyright 2017 ABB. All rights reserved
Value when activated Value when
1
2
4
8
16
32
64
128
256
512
1024
2048
4096
8192
16384
32768
GUID-1913E066-37D1-4689-9178-5B3C8B029815 v3
ANSI/IEEE C37.2 device
number
-
GUID-B4B47167-C8DE-4496-AEF1-5F0FD1768A87 v2
1MRK 511 401-UUS F
deactivated
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Bay control REC670