ABB Relion 670 Series Applications Manual page 356

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 14
Control
289OPTR (bay 1/sect.B1)
289OPTR (bay n/sect.B1)
VP289TR (bay 1/sect.B1)
VP289TR (bay n/sect.B1)
EXDU_DB (bay 1/sect.B1)
EXDU_DB (bay n/sect.B1)
ANSI04000501 V1 EN-US
Figure 160: Signals from double-breaker bays in section B1 to a bus-section disconnector
For a bus-section disconnector, these conditions from the B2 busbar section are valid:
289OPTR (bay 1/sect.B2)
289OPTR (bay n/sect.B2)
VP289TR (bay 1/sect.B2)
VP289TR (bay n/sect.B2)
EXDU_DB (bay 1/sect.B2)
EXDU_DB (bay n/sect.B2)
ANSI04000502 V1 EN-US
Figure 161: Signals from double-breaker bays in section B2 to a bus-section disconnector
14.4.6.4
Signals in breaker and a half arrangement
If the busbar is divided by bus-section disconnectors, the condition for the busbar disconnector
no other disconnector connected to the bus-section must be made by a project-specific logic.
bay
The same type of module (A1A2_DC) is used for different busbars, that is, for both bus-section
disconnector A1A2_DC and B1B2_DC. But for B1B2_DC, corresponding signals from busbar B are
used.
(WA1)A1
(WA2)B1
ANSI04000503 V1 EN-US
Figure 162: Busbars divided by bus-section disconnectors (circuit breakers)
350
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
Section 1
A1A2_DC(BS)
B1B2_DC(BS)
BH_LINE
BH_LINE
© Copyright 2017 ABB. All rights reserved
S1DC_OP
AND
VPS1_DC
AND
EXDU_BB
AND
en04000501_ansi.vsd
S2DC_OP
AND
VPS2_DC
AND
EXDU_BB
AND
en04000502_ansi.vsd
Section 2
A2
B2
BH_LINE
BH_LINE
en04000503_ansi.vsd
1MRK 511 401-UUS F
M13542-127 v5
Bay control REC670
Application manual