ABB Relion 670 Series Applications Manual page 445

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UUS F
16.12.3
Setting guidelines
The settings
resolution of the settings depends on the level of the values defined.
A resolution of 10 ms can be achieved when the settings are defined within the range
1.00 second ≤ tAlarm ≤ 99 999.99 seconds
1.00 second ≤ tWarning ≤ 99 999.99 seconds.
If the values are above this range, the resolution becomes lower due to the 32 bit float
representation
99 999.99 seconds < tAlarm ≤ 999 999.0 seconds
99 999.99 seconds < tWarning ≤ 999 999.0 seconds
The limit for the overflow supervision is fixed at 999999.9 seconds.
16.13
Comparator for integer inputs - INTCOMP
16.13.1
Identification
Function description
Comparison of integer values
16.13.2
Application
The function gives the possibility to monitor the level of integer values in the system relative to
each other or to a fixed value. It is a basic arithmetic function that can be used for monitoring,
supervision, interlocking and other logics.
16.13.3
Setting guidelines
For proper operation of comparison the set value should be set within the range of ± 2 ×10
Setting procedure on the IED:
EnaAbs : This setting is used to select the comparison type between signed and absolute values.
Absolute : Comparison is performed on absolute values of input and reference values
Signed : Comparison is performed on signed values of input and reference values.
Bay control REC670
Application manual
tAlarm and tWarning are user settable limits defined in seconds. The achievable
tAlarm and tWarning are independent settings, that is, there is no check
Note that
if
tAlarm > tWarning .
IEC 61850
identification
© Copyright 2017 ABB. All rights reserved
IEC 60617
identification
INTCOMP
Int<=>
GUID-2911D624-87D5-4427-BB2F-E0D1072394FA v3
GUID-5992B0F2-FC1B-4838-9BAB-2D2542BB264D v1
ANSI/IEEE C37.2
device number
GUID-4C6D730D-BB1C-45F1-A719-1267234BF1B9 v1
GUID-ADA3E806-BEF1-4D15-B270-207386A0AEE4 v2
Section 16
Logic
9
.
439

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec670

Table of Contents