Installing 4-Wire Class A Smoke Detectors; Conventional Notification Appliance - Honeywell Silent Knight SK318PT Installation And Operation Manual

Addressable fire system, emergency voice system
Table of Contents

Advertisement

3.
The detector gets smoke power from Flexput 6 circuit and the contact input is connected to Flexput 5 circuit.
NOTE: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is used to refer to the circuit pair. In this
example, Figure 4.49 uses both Flexput circuit 5 and 6, so in programming it would be referred to as point 5.

Installing 4-Wire Class A Smoke Detectors

Figure 4.50 illustrates how to install a 4-wire Class A detectors.
Conventions used for wiring 4-wire Class A loop:
1.
One Class A 4-wire loop can be connected to the control panel.
2.
Smoke power is supplied to each Class A loop as shown in Figure 4.50.
NOTE: In programming any point that uses multiple Flexput circuits are always referred to as the lowest Flexput circuit number used. In this
example, Figure 4.50 uses Flexput circuits 5, 6 together with NAC 4. In programming (4, 5, 6) would be referred to as point 5.

4.16 Conventional Notification Appliance

This sub-section of the manual explains how to install conventional notification appliances for Class A and Class B configurations.
6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017
Supervised
power limited
Figure 4.49 Class B 4-Wire Smoke Detector Connections
Figure 4.50 Class A 4-Wire Smoke Detector Connections
4.7 kEOL
Air Products
PAM-2
Model 160150
Supervision
Module
Air Products
PAM-2 Model
160150
Supervision
Module
59

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Silent knight 6820Silent knight 6820evs

Table of Contents