4.9 6815 Installation

The 6815 SLC expander lets you add 159 SK detectors and 159 SK modules. The maximum number of SLC devices per panel is 1110.
The number of 6815's is limited by the maximum number of SBUS devices.
NOTE: 6815 will only support SK or SWIFT
To install the 6815:
1.
Make sure power is off at the panel.
2.
Mount the 6815 in the 6820 cabinet, the 5895XL cabinet, or the 5815RMK remote mounting kit. Use the standoffs located under
the control panel board assembly and secure with screws provided with the 6815. For additional information, also see Model
5895XL Installation Instructions (P/N 151142) or 5815RMK Remote Mounting Kit Installation Instructions (P/N 151391).
3.
Connect the 6815 to the control panel. (See Section 4.8.1.)
4.
Use on-board DIP switches to select an SBUS ID#. (See Section 4.13.1).
5.
The new 6815 module must be added to the system through programming. JumpStart will add the module automatically (see
Section 8.1). You can also add it manually (see Section 9.2.2). Select a name, if desired.
6.
You are now ready to connect SLC devices to the 6815 (see Section 9.5.1).
Figure 4.31 is a drawing of the 6815 board, showing the location of terminals and DIP switches
6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017
®
SLC device
Figure 4.31 6815 Board
47