Type Selection
SWITCH
(cont.)
6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017
Function
Latching Option
MANUAL PULL
WATERFLOW
Latching
Non Latching
FIRE SUPER-
Latching
VISORY
Non Latching
FIRE DRILL
SILENCE
RESET
P.A.S. ACK
ZONE AUX1
Latching
Non Latching
ZONE AUX2
Latching
Non Latching
SYSTEM AUX1
Latching
Non Latching
SYSTEM AUX2
Latching
Non Latching
DETECTOR
FIRE TAMPER
Latching
Non Latching
MANUAL
RELEASE
INTERLOCK
STATUS POINT
Table 9.4 Point Programming for 6815
Comments
Use this switch type for manual pull stations. This input is always
latched. The switch can clear only when an alarm is reset. This
switch type has the highest fire priority; it overrides any other type of
fire alarm.
Use this switch type for monitoring water flow in a sprinkler system.
Switch closure will cause a sprinkler alarm. Water flow switches can
be programmed as latching or non-latching.
You can program a delay of up to 90 seconds to be used with a
water flow switch. The delay allows for normal, brief changes in
sprinkler system water pressure. The water flow alarm will not
activate unless the switch is active for the programmed delay time.
If a delay is used, the system begins counting down when the switch
closes. If the switch opens (restores) before the timer expires, a
water flow alarm is not generated. If the water flow switch remains
closed after the timer expires, a water flow alarm will be generated.
Use this switch type for tamper monitoring of sprinklers and other
fire protection devices. If a contact closes, a sprinkler supervisory
event will be generated. Supervisory switches can be latching or
non-latching.
System-level, non latching switch. This switch is an alternative way
of causing a fire drill. It has the same operation as the fire drill option
available from the annunciator. When the switch is activated, a fire
drill begins; when the switch is de-activated, the fire drill ends.
This system-level switch is an alternative way to silence the fire
system. It has the same effect as pressing the Silence key.
This system-level switch is an alternative way to reset the fire
system. It has the same effect as pressing the Reset key.
Positive acknowledge switch. This switch must be used in zones
programmed as Positive Alarm Sequence (see "Edit Zone
Properties" on page 116 "Table 9.1 list the detector characteristics
and a description of each.").
If an acknowledge switch closes when an alarm or trouble condition
is not already in progress, a trouble will occur.
You must use a UL listed normally open, momentary switch type.
The switch must be rated at 5V, 100 mA (minimum) and be used
with an EOL resistor for supervision.
Use these switch types if you want to monitor special zone-level
conditions (such as dry contact from a remote power supply).
Use these switch types if you want to monitor special system-wide
conditions (such as dry contact from a remote power supply).
Used to monitor conventional 4-wire detectors, a contact closure will
generate a detector alarm event.
Performs identically to a supervisory switch, but will be indicated as
a tamper switch on the LCD annunciator.
Manual release switch
Interlock release switch input.