10.6.1 Multi-Site Annunciator and Multi-Site User Access
Multi-site Annunciators are unique as they can display the status and event history of all sites they are assigned to. These displays can be
especially useful in guard shacks or security centers. A multi-site display is indicated by the words "Multi-Site Display" at the top of the
idle screen.
1.
The F-Macro key is disabled until a multi-site user access code has been entered and a specific site has been selected.
2.
Multi-site Annunciator silencing rules:
If any new troubles, supervisory, pre-alarms, or alarms are triggered in any assigned sites, Locally Silenced
annunciator will resound.
If a multi-site annunciator is locally silenced for 4 or 24 hours depending on user selection, the locally
silenced annunciator will resound.
3.
The 6820 or 6820EVS menu system is disabled on a multi-site annunciator. Pressing the Right or Enter keys will bring you straight
into event history for assigned sites. To get into the menu system, a multi-site user password must be entered and then a site must be
selected from the site selection menu. Once this is done you will have access to the idle screen of that site and the annunciator will
temporarily act like a single site annunciator.
4.
A multi-site annunciator will sound the highest priority tone from the sites it is assigned to.
NOTE: A multi-site display is created in Module programming in the edit properties menu for an 6860, 5860 or 6855 See section 9.2.1.
NOTE: An annunciator cannot be programmed as a multi-site display when it is associated with an VCM or RVM in a EVS system.
NOTE: Status Points, Status Voice Aux 1, Status Voice Aux 2, and Background Music are contained within the System Status event priority.
NOTE: All fire, emergency and system troubles are prioritized into the Trouble event priority.

10.7 Releasing Operations

The control panel supports two types of releasing: Double Interlock Zone, and Single Interlock Zone. The Double Interlock Zone opera-
tion requires an interlock switch input in the system, and the Single Interlock Zone does not. An interlock switch is typically a dry-con-
tact pressure switch.
When Single or Double Interlock Zone releasing is selected using HFSS Honeywell Fire Software Suite software, the software suite will
automatically default the following system parameters:
NOTE: The defaults created can be modified through programming if desired.
Output Group 2 is created. Output Group 2 will be defaulted as a "Detector Alarm" output group for all releasing zones. NAC
[98:001] is assigned to Output Group 2.
Output Group 3 is created. Output Group 3 will be defaulted as a "Interlock Release Alert" output group for all releasing zones.
NAC [98:002] is assigned to Output Group 3.
Output Group 4 is created. Output Group 4 will be defaulted as "Interlock Release Alarm" output group for all releasing zones.
NAC circuit [98:003] is assigned to Output Group 4..
NOTE: The installer must define which input points will be used for detectors, manual release switches, or interlock/pressure switches.
NOTE:
For manual release operation, Installer must use an FM approved/ UL listed releasing manual station
6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017
System Behavior
SYSTEM SILENCE LED is on. SYSTEM
TROUBLE, SUPERVISORY or GENERAL
ALARM LED (depending on condition) is on.
The annunciator (and any notification devices
attached to the system) will be silenced.
Table 10.2 :Operation Mode Behavior
In This Mode You Can
Press down arrow to view the location of the alarm or
trouble. When the condition no longer exists, the
SYSTEM SILENCED and SYSTEM TROUBLE LED,
SUPERVISORY or GENERAL ALARM LEDs turn off.
145